GSC53N - GSC57 - ZG47
EN - 23
6.2.2. Results of "MAN" mode
At the end of the test if
the Insulation resistance
is
lower than R
MAX
(see
Table2), upper to set
limit value
and the
instrument generated
the
Nominal
test
Voltage
, the instrument
emits a
double sound
signal
indicating the
positive outcome of
the test
and displays
one screen similar to
the screen alongside.
M
05.06.02
Insulation Resistance
1.07
M
514V 15s
Voltage during the Test
Duration of the Test
Test mode
OK
MAN 500V LIM: 0.50M
Set limit value
FUNZ VNOM
Nominal voltage test
The displayed result can be stored pressing the
SAVE
key
twice
(according to
paragraph 9.1).
If
the
Insulation
resistance is
higher
than R
MAX
(see Table2),
the instrument emits a
double sound signal
at
the end of the test
indicating the positive
outcome of the test
and displays one screen
similar to the screen
alongside.
M
05.06.02
Maximum resistance value
which can be measured
(999 is displayed if a
rated voltage of 500V was
selected see Table2).
> 999
M
523V 15s
Duration of the Test
OK
MAN 500V LIM: 0.50M
FUNZ VNOM
The displayed result can be stored pressing the
SAVE
key
twice
(according to
paragraph 9.1).