GSC53N - GSC57 - ZG47
EN - 93
8.6.2. "METER" mode
In this mode the instrument shows one of the below screens according to the settings
made as per paragraph 8.1.
27.09.00 17:35:12
27.09.00 17:35:12
27.09.00 17:35:12
POWER
SINGLE PHASE
V1 = 230.0 V
I1 = 145.3 A
P1 = 32.91 kW
Q1 = 5.767 kVAR
S1 = 33.41 kVA
pf1 = 0.99 i
dpf1 = 0.99 i
POWER
THREE WIRE
Pt = 64.19 kW
Qt = 10.99 kVAR
St = 65.12 kVA
pft = 0.99 i
dpft = 1.00 i
POWER
THREE PHASE
Pt = 135.8 kW
Qt = 24.59 kVAR
St = 138.0 kVA
pft = 0.98 i
dpft = 1.00 i
Phseq= 123
WAVE
PG-
PG+
ChgP WAVE
PG-
PG+
ChgP WAVE
PG-
PG+
Example of screen in single-
phase mode
Example of screen in “3 wires”
three-phase mode
Example of screen in “4 wires”
three-phase mode
The symbols used are described in Table 9
For any message displayed see Appendix 1 – MESSAGES DISPLAYED.
Following keys are enabled:
F1
:
(only for three-phase measurement) to display cyclically the following
screen (according to settings made as per paragraph 8.1):
Three-phase 3 wires: total three-phase values, Wattmeter phases 1-2 and 2-3 values, Peak Demand
Three-phase 4 wires: total three-phase values, phase1, phase2 and phase3 values, Peak Demand
F2
:
to pass to "WAVE" mode (see paragraph 8.6.3).
F3/F4
:
to pass to previous/next function respectively.
SAVE
:
to save in the instrument memory a record of “Smp” type (see
paragraph 9.2) and the instantaneous values of voltage and current
present on the instrument inputs. This function is disabled during a
recording.
ENTER/HOLD
: to enable/disable the HOLD function (updating interruption) of the
displayed data. All the previous functions remain however available.
When the HOLD function is enabled, the word
HOLD
is displayed.
When this function is enabled it’s not possible to record or take an
energy measurement. This function is disabled during a recording or
an energy measurement.
MENU
:
to enter in the
MENU
mode and change the instrument settings (see
paragraph 8.1 and 8.2). It’s not possible to enter the configuration
MENU during a recording or an energy measurement.
START/STOP
: to record
selected parameters
according to the instrument’s settings
(see chapter 10).
Содержание GSC53N
Страница 1: ...Copyright HT ITALIA 2012 Release EN 1 08 28 02 2012 GSC53N GSC57 ZG47 Instruction Manual...
Страница 2: ......
Страница 151: ......