SV2 Series Safety Shut-off Valves
24
32-00029—02
Table 5. Valve Pressure Access Ports.
Location
Valve Pressure
Access
Locations
1
Pressure Port
Label
Pressure
Measurement
Usage
2
Inlet Flange
-
-
Inlet
Inlet pressure measurement
C6097 NPT or Rp mount pressure switch for low
gas limit
Valve Seat
1
A
C
I
Inlet
Inlet pressure measurement
C6097 NPT or Rp mount pressure switch for low
gas limit
NOTE: Cannot be used with Pressure Module
M
Mid
Mid-valve seat pressure measurement (between V1
and V2)
C6097 flange mount pressure switch for external
VPS
Pressure Module for low + high gas limits, VPS, leak
detection
R
Regulator Servo Future usage
Valve Seat
2
B
D
M
Mid
Mid-valve seat pressure measurement (between V1
and V2)
O
Outlet
Outlet pressure measurement
C6097 flange mount pressure switch for high gas
limit
Pressure Module for low + high gas limits
R
Regulator Servo Future usage
Outlet Flange
-
-
Outlet
Outlet pressure measurement
C6097 flange mount pressure switch for high gas
limit
1.
Locations A, B, C and D have embedded guide posts for Pressure Module and C6097 keyed mounting orientation.
2.
Usage is valve model dependent due to available open ports. For detailed C6097 and Pressure Module usage and installation instructions, refer to the SV2