SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
Deleting Points on the Correction Curve (Deletion button)
Single points can be deleted by picking the desired point in the selection box and pushing the Delete single button. The
selected point will turn red in the graph and is identified by the X-axis value and the point number counting from left to
right.
After deleting the minimum or maximum point, the system will generate a warning. A new value for the minimum and
or maximum needs to be defined to be able to run the system in normal operation mode (Not Installer or OEM mode).
All points of the curve can be deleted at once by selecting Delete all button. The gain setting will default to 1. To be
able to run the system in normal operation mode, a minimum of 4 points need to be defined (Minimum, Maximum and
two intermediate points).
Fuel-Air Curves Summary
Refer to
Fig. 58
. After completing setup of the Base and Correction Curves, both curves may be viewed on the summary page or
tab. The values can be viewed in chart or table formats.
Fig. 58: Fuel-Air Curves Summary.
Combining All of the Parameter Concepts for Ignition Setup
Together, all the parameters from the OEM Setup, Ignition Setup, Base Curve and Correction Curve can be used for initial
ignition setup and subsequent ignition optimization.