SV2 Series Safety Shut-off Valves
167
V2F, V2V
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
SOLA Controller
LIMIT CONTROL
INPUT
RECTIFIER
V1
RECTIFIER
V2
INTERNAL
ELECTRONICS
N
RUN/LOCKOUT
INTERLOCKS
OPTIONAL
ILK WIRING
L1
L1
SV2 SERIES VALVE
1 MATCH SV2 SERIES VALVE AND FLAME
SAFEGUARD VOLTAGES.
ILK (INTERLOCK) WIRING RUN THROUGH
THE SV2 SERIES VALVE FOR SOLENOID
POWER SAVING FEATURE. APPLICABLE
TO ALL SV2 SERIES VALVE MODELS.
WHEN THE SV2 SERIES VALVE PRESSURE
MODULE IS ENABLED, PROGRAMMED
AND USED FOR LOW GAS PRESSURE
AND HIGH GAS PRESSURE LIMITS, THE
LIMITS ARE INCLUDED IN THE INTERNAL
ILK (INTERLOCK) VALVE STRING. BASIC
(5) ELECTRONICS VALVES DO NOT HAVE
THE ABILITY TO INTERFACE WITH THE
SV2 SERIES VALVE PRESSURE MODULE.
AN EXTERNAL PRESSURE SWITCH MUST
BE USED WITH THESE VALVE MODELS.
OBSERVE FLAME SAFEGUARD WIRING
PER ITS MANUAL.
IF SOLA INTERNAL OPERATING
CONTROL IS USED, EXTERNAL
CONTROL WIRING NOT APPLICABLE.
2
2
RM791X
SOLA
ILKOUT
MV1
MV2
ILKIN
POC
VPS
L1
N
GROUND
3
3
5
4
4
4
5
CONTROL
LIMITS
INTERLOCKS
PRE-IGNITION
INTERLOCK
MAIN VALVE 1/2
1
1
M35594B
L1
INDICATES FEEDBACK SENSING OF
RELAY CONTACT STATUS AND LINE
VOLTAGE.
SOLA CONTROLLER
J6
T5
J6
T3
J5
T1
J5
T3
6
6 POC (PROOF OF CLOSURE) MUST BE
FACTORY INSTALLED, INTERNALLY
WIRED AND CALIBRATED.
Fig. 149: SOLA with STANDARD Electronics, No External VPS.