SV2 Series Safety Shut-off Valves
214
32-00029—02
Address
Type
Valve
Model
Intelligence
Level
Description
Data
Type
Content
Range
Default
Value
Dec
Hex
Min
Max
156
9C
HGP /
LGP
All
Standard
Low gas pressure (LGP) limit
lockout type
Enum
0=Disabled
1=Auto reset
2=Manual reset
Other value invokes an invalid setup
0
2
157
9D
High gas pressure (HGP) limit
lockout type
Enum
0=Disabled
1=Auto reset
2=Manual reset
Other value invokes an invalid setup
0
2
159
9F
% of measured operating
pressure used to set the High
gas pressure (HGP) limit during
setup.
S16
Value in %
% offset = +100%
25
50
160
A0
% of measured operating
pressure used to set the Low gas
pressure (LGP) limit during setup.
S16
-50
-25
161
A1
Low gas pressure (LGP) and
High gas pressure (HGP) setup
indication
S16
0 =LGP limit set value is valid
1 =LGP pressure value too low
2 =LGP selection is below usable pressure
module range
3 =LGP pressure value too high
8 =HGP limit set value is valid
9 =HGP pressure value too low
10=HGP selection is below usable pressure
module range
11=HGP pressure value too high
-32768
32767
0
162
A2
Calculated Low gas pressure
(LGP) Limit Set Point in user
selected pressure units.
Based on selected Lo-Gas Limit
% of operating pressure and
actual measured Operating
Pressure during setup (refer to
Holding Register 160).
U16
0=Invalid value
Pressure in user selected units.
See Holding Register 74 for selected units.
163
A3
Calculated High gas pressure
(HGP) Limit Set Point in user
selected pressure units.
Based on selected Hi-Gas Limit %
of operating pressure and actual
measured Operating Pressure
during setup (refer to Holding
Register 159).
U16
0=Invalid value
Pressure in user selected units.
See Holding Register 74 for selected units.
150
96
VPS
All
Standard
VPS disable / enable status
Bool
0=VPS disabled
1=VPS enabled
0
1
151
97
Max allowed leakage in user units
U16
Volumetric flow.
See Holding Register 75 for selected units.
28 L/h
Refer to
Table 37
NV
152
98
Space between valves volume.
Units according to selected
volumetric units.
U16
Volume.
See Holding Register 78 for selected units.
Refer to
Table 37
Refer to
Table 37
NV
153
99
Extra chamber space for external
piping between V1 and V.
Units according to selected
volumetric units
U16
Volume.
See Holding Register 78 for selected units.
0
Refer to
Table 37
NV
154
9A
VPS relay polarity.
Selectable action during setup.
Bool
0=Pressure to close
1=Pressure to open
0
1