SV2 Series Safety Shut-off Valves
124
32-00029—02
Fig. 85: OEM Reset Password Changed confirmation dialog box.
Access Levels Assignment
After the password assignments are complete, the next step in the guided setup sequence is the Access Levels assignment. This
page can also be reached via the Setup & Tests --> Settings --> Access Levels menus. Refer to
Fig. 86
.
The user must be logged in as the OEM in order to assign applicable user access to each of the parameter groupings. For the
items included in each group, refer to
Table 25
. Applicable access level choices from the drop down menus are OEM, Installer
and Read Only. The default for all parameter groups is Installer. Refer to
Fig. 86.
₀ If OEM is chosen, only the OEM may make changes to the associated parameters within that grouping when logged in as
the OEM.
₀ If Installer is chosen, both the Installer and the OEM may make changes to the associated parameters within that
grouping when logged in as the Installer or the OEM.
₀ If Read-Only is chosen, neither the Installer nor the OEM can make changes to the associated parameters. In order to
make changes possible, the OEM would have to change the Access Level to the OEM or Installer levels.
₀ For the Remote Reset parameter group only, there is also an Anonymous selection, which allows anyone to remotely reset
the valve via the user interface. Therefore the access level can be Anonymous, Installer, OEM or Read-only.
NOTE: The Installer automatically has access to the Safety Parameter Verification function for any parameter groups
regardless of access level configuration.
In order for the Installer to perform a FARMOD replacement in the field, the OEM must grant them access to the
following Valve Access Levels (refer to
Fig. 87
):
• FARMOD
• FAR Correction Curve
The Set Access Levels to Default button can only be used when logged in as the OEM to reset all of the settings to the Honeywell
default settings as shown in
Fig. 86
.
NOTE: The Access Level parameter grouping assignments are included in the OEM cloning procedure and thus will be
copied to new valves with the same access level assignments as the original valve setup being cloned.