SV2 Series Safety Shut-off Valves
141
V2F, V2V
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
a. Select the ‘Connect New Valve’ button to connect another valve and/or clone another valve. The user is redirected to the
Home page where another valve can be selected for cloning or any connected valve can be selected for viewing status.
b. Select the ‘Finish Setup’ button to finalize the valve cloning procedure and return to the Valve Status page (refer to
Fig.
111
).
12.
After cloning is complete, start the valve in the Installer or OEM mode and set the new fuel/air Correction Curve and record
the Ign. Air Level to make the valve fully operational.
Configured Valve Procedure
1.
With the valve connected to the user interface (HMI Tool or PC Tool), navigate to the Home page. The attached configured
valve(s) are identified via a date stamp at the bottom of the valve tile(s). Refer to
Fig. 111
.
Fig. 111: Configured valve tile on user interface.
2.
Select the appropriate connected valve tile. The valve status page will be displayed. Refer to
Fig. 112
.
Fig. 112: Valve status page.
3.
Select the ‘Setup & Tests’ tile on the valve status page. This will open the ‘Setup & Tests’ page. Refer to
Fig. 113
.