SV2 Series Safety Shut-off Valves
224
32-00029—02
Address
Type
Valve
Model
Intelligence
Levels
Description
Data
Type
Content
Dec
Hex
9
9
Fuel / Air
V2V
Standard
Filtered S1 sensor signal
S16
Dimensionless
- Represents mass flow of air in the appliance.
- Can also represent gas flow in the appliance if the Lambda
value is held constant.
- When linking this value to fan speed, consideration must be
given to relative changes in air density.
12
C
Stepper motor maximum number of steps.
This value corresponds to the fully opened valve
U16
Position scaled by 4
(i.e. value of 4 is one full step)
13
D
Valve target ignition position 2 in motor steps during
ignition ramp time
U16
Position scaled by 4
(i.e. value of 4 is one full step)
49
31
Fuel/Air Module EEPROM status
Ehum
0 =There has not been communication with EEPROM
1 =Communication with EEPROM is OK
3 =EEPROM data matches RAM storage
0x81=Communication error
0x82=EEPROM writing failed
0x84=RW data inconsistency
0x88=RO data inconsistency
52
34
Fuel/Air Module status
Enum
0 =Disabled
1 =Enabled
3 =OK
0xA1=EEPROM data inconsistency
0xC1=Communication error
125
7D
Ignition Learnt Pos. 2
S16
Position scaled by 4
(i.e. value of 4 is one full step)
127
7F
Full valve stroke in motor steps
S16
Position scaled by 4 (i.e. value of 4 is one full step) run
between end stops in the last detection cycle.
297
129
Target amplification
S16
Current gain value based on current fuel/air curve and
settings.
Value scaled by 1x104
298
12A
Fuel/air curve informational flags related to curve
loading and saving
U16
Bit 0: True = if new curve point is added, it will replace
another existing point. 0 = a new point will be added to the
curve.
Bit 1: True/False = the fuel/air curve commissioning mode
is active/inactive.
Bit 2: True = a fuel/air curve maximum point already exists.
Bit 3: True = point commissioning is currently active.
Bit 4: True = a fuel/air curve minimum point already exists.
Bit 5: True = an initial fuel/air curve already exists.
Bit 6: True = a fuel/air curve point is being sampled.
Bit 7: True = the fuel/air curve is locked.
Bit 8: True = the loaded fuel/air curve data is OK and can
be stored. Updated when the fuel/air curve is unlocked for
editing.
Bit 9: True = a new fuel/air curve point has been saved.
349
15D
X-coordinate 0
S16
X-coordinate of CORRECTION fuel/air curve, S1 sensor
value.
S1 value is dimensionless.
-32768 indicates an empty cell
350
15E
X-coordinate 1
351
15F
X-coordinate 2
352
160
X-coordinate 3
353
161
X-coordinate 4
354
162
X-coordinate 5