SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
Fig. 140: Proof of Closure Switch tab.
7.
Perform the Safety Parameter Verification procedure by selecting the Verify Safety Parameters button at the bottom of the
POC tab.
Fig. 141: Safety Parameters Verification page.
8.
After cloning and the above steps are complete, start the valve in the Installer or OEM mode and commission the Pressure
Module Lo-Gas and Hi-Gas settings, if used, to make the valve fully operational:
a. Note that the Fuel/Air valve (V2V models) Base Curve, Correction Curve and Pre-Ignition calibration settings are restored
from the connected FARMOD upon valve power-up.
b. Pressure Module Lo-Gas and Hi-Gas limit settings. Refer to
Fig. 142
.
• Navigate to the Setup & Tests menu.
• Select the Hi-Gas & Lo-Gas Pressure tile.
• Accept the warning statement.
• Choose the Hi-Gas or Lo-Gas tab.
• Run the burner as specified, allowing the pressure to stabilize. Select the Set Limit button to set the applicable
pressure limit. Repeat with the remaining limit setting.