SV2 Series Safety Shut-off Valves
220
32-00029—02
Address
Type
Valve
Model
Intelligence
Levels
Description
Data
Type
Content
Dec
Hex
32
20
Pressure
Module
All
Standard
Current Pressure Module pressure reading.
Shown in user selected pressure units.
U16
Pressure.
See Holding Register 74 for selected units.
33
21
Pressure Module status
Enum
0 =Operation is not requested
1 =Powered but communication not established
3 =Operating correctly
0x82=Parameters are not valid
0x83=PM used is out of acceptable range
0x85=PM has not been accepted via programming tool
0x89=Sensor state error
0x91=Sensor value comparison error
0xA1=PM EEPROM has not been detected
0xC1=Sensor communication error
34
22
Pressure Module temperature
S16
Pressure Module measured temperature in selected units
36
24
Pressure Module sensor 1 status
Enum
0=No communication established with sensor
1=Sensor is operating correctly
2=Sensor is in command mode
4=Sensor diagnostic error
8=Communication error
37
25
Pressure Module sensor 2 status
Enum
38
26
Pressure Module sensor 3 status
Enum
39
27
Pressure Module EEPROM status
Enum
0 =There has not been communication with EEPROM
1 =Communication with EEPROM is OK
3 =EEPROM data matches RAM storage
0x81=Communication error
0x82=EEPROM writing failed
0x84=RW data inconsistency
0x88=RO data inconsistency
41
29
Pressure Module sensor 1 serial number
U16
Number
43
2B
Pressure Module sensor 2 serial number
U16
Number
45
2D
Pressure Module sensor 3 serial number
U16
Number
320
140
POC
All
Standard
Proof of Closure 1 (POC 1) status
Enum
0 =POC reading and function disabled
1 =POC detected, but not activated by user
2 =Reading indicates closed valve
3 =Reading indicates open valve
0x10=Not calibrated
0x80=Reading error
321
141
Proof of Closure 2 (POC 2) status
Enum
326
146
Proof of Closure (POC) relay output status
Enum
0 =POC output is off
1 =POC output is on
0x80=Voltage detected on POC output while relay is off
337
151
MV1 closing time
S16
Time in milliseconds as measured using POC (-1=is not
measured)
339
153
MV2 closing time
S16
26
1A
VPS
All
Standard
Minimum allowed VPS test pressure.
Shown in user selected pressure units.
U16
Pressure.
See Holding Register 74 for user selected units.
55
37
VPS minimum calculated valve powered time
requirement for burner control
U16
Time in seconds
56
38
VPS Valve 1 status
Enum
0 =Test has not been performed yet
1 =Test was started
3 =Leakage has been calculated
4 =Test is finished
0x83=Leakage is over leakage limit
0x84=Wrong pressure level detected during initialization
of VPS test
0xFF=VPS function disabled