SV2 Series Safety Shut-off Valves
217
V2F, V2V
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
Address
Type
Valve
Model
Intelligence
Level
Description
Data
Type
Content
Range
Default
Value
Dec
Hex
Min
Max
391
187
Fuel/Air
V2V
Standard
Fuel/air correction curve name
entered by user
U16
Fuel/air curve name 0
0
65535
0
392
188
U16
Fuel/air curve name 1
0
65535
0
393
189
U16
Fuel/air curve name 2
0
65535
0
394
18A
U16
Fuel/air curve name 3
0
65535
0
395
18B
U16
Fuel/air curve name 4
0
65535
0
396
18C
U16
Fuel/air curve name 5
0
65535
0
397
18D
U16
Fuel/air curve name 6
0
65535
0
398
18E
U16
Fuel/air curve name 7
0
65535
0
771
303
Base Curve length
S16
Number of fuel/air Base Curve points that
have been received via Modbus during the
lock process.
-32768
32768
-32768
779
30B
S1 minimum threshold
U16
A % that the air S1 signal can be below the
recorded / commissioned minimum air
signal of the Correction Curve during normal
RUN mode at minimum load.
If the S1 signal drops below this value, the
valve is cycled off and waits for S1 to rise
above this value. The valve does not lockout.
50
95
80
780
30C
S1 maximum threshold
U16
A % that the air S1 signal can be over the
recorded / commissioned maximum air
signal of the Correction Curve during normal
RUN mode at maximum load.
If the S1 signal rises above this value, the
valve is cycled off and waits for S1 to drop
below this value. The valve does not lockout.
105
150
120
473
1D9
POC
All
Standard
POC (Proof of Closure) Setup
indication
Enum
0= There is no POC function activated
1= POC activated on MV1 only
2= POC activated on MV2 only
3= POC activated on both MV1 and MV2
0
0x55
0 (NV)
791
317
Secure
Modbus
All
Standard
Active User
U16
Information about current active user mode
795
31B
Security Flags
U16
Bit 0: Enable Installer password reset
Bit 1: Enable OEM password Reset