SV2 Series Safety Shut-off Valves
221
V2F, V2V
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
Address
Type
Valve
Model
Intelligence
Levels
Description
Data
Type
Content
Dec
Hex
57
39
VPS
All
Standard
VPS Valve 2 valve status
Enum
0 =Test has not been performed yet
1 =Test was started
3 =Leakage has been calculated
4 =Test is finished
0x83=Leakage is over leakage limit
0x84=Wrong pressure level detected during initialization
of VPS test
0xFF=VPS function disabled
58
3A
Input pressure measured during VPS
U16
Pressure.
See Holding Register 74 for user selected units.
59
3B
Output pressure measured during VPS
U16
60
3C
Valve 1 maximum leakage detected during last VPS
sequence.
Shown in user selected flow units.
S16
Volumetric flow.
See Holding Register 75 for selected units.
61
3D
Valve 2 maximum leakage detected during last VPS
sequence.
Shown in user selected flow units.
S16
Volumetric flow.
See Holding Register 75 for selected units.
62
3E
VPS minimum test time requirement for burner
control
S16
Time in seconds
270
10E
Valve 1 accumulated hours recorded during
last VPS sequence
U16
Upper word
271
10F
U16
Lower word
272
110
Valve 1 accumulated cycles recorded during
last VPS sequence
U16
Upper word
273
111
U16
Lower word
274
112
Valve 2 accumulated hours recorded during
last VPS sequence
U16
Upper word
275
113
U16
Lower word
276
114
Valve 2 accumulated cycles recorded during
last VPS sequence
U16
Upper word
277
115
U16
Lower word
682
2AA
VPS recorded leakage rate for MV1
S16
Expressed in units selected by user during setup
683
2AB
Number of averaged VPS measurements for MV1
U16
Dimensionless number
684
2AC
Recorded valve cycles during MV1 VPS test
U16
Upper word
685
2AD
U16
Lower word
686
2AE
VPS test execution time for MV1
U16
Upper word, resolution 0.25 hours
687
2AF
U16
Lower word, resolution 0.25 hours
689
2B1
VPS recorded leakage rate for MV2
S16
Expressed in units selected by user during setup
690
2B2
Number of averaged VPS measurements for MV2
U16
Dimensionless number
691
2B3
Recorded valve cycles during MV2 VPS test
U16
Upper word
692
2B4
U16
Lower word
693
2B5
VPS test execution time for MV2
U16
Upper word, resolution 0.25 hours
694
2B6
U16
Lower word, resolution 0.25 hours
Note:
Input registers 139 – 213 contain the fault history. The last 15 fault records are stored. Each record consists of 5 consecutive input registers; 1 input register holds the fault code, 2 input registers hold
the time stamp and 2 input registers hold the valve cycle count recorded at the moment of fault occurrence. The time stamp is recorded with resolution 0.25 hr.
The 4 time stamp / cycle count input registers for each fault contain a 32-bit value stored in mode 3-2-1-0. The input register with lower number contains the upper bytes of the 32-bit number (bytes 3 and
2) and the input register with higher number contains the lower bytes of the 32-bit number (bytes 1 and 0).