
SV2 Series Safety Shut-off Valves
110
32-00029—02
•
Fig. 65
and
Fig. 66
show examples of an amplification factor control characteristic Base Curve and Correction Curve with 6
setpoints in the Base Curve and 4 points in the Correction Curve after finishing the setup procedure.
• Modifying the Base Curve leads to erasing the Correction Curve. Therefore, it is better to make small modifications to the
Correction Curve instead of making adjustments to the Base Curve.
Fig. 65: Amplification factor control Base Curve.
Fig. 66: Gain factor Correction Curve after Set Max Completed.
NOTE: If the Enter Optional Data box is checked, you will be asked to enter the measured O2 level and fan speed values
before storing the individual amplification factors.
Valve Production Cloning
Provisions for customer production cloning of established valve parameters have been added to the HMI and PC Tools. The
Valve Production Cloning page provides a shortcut for factory production and cloning of established valve configurations as
well as cloning for certain field situations. For detailed step-by-step production cloning procedures, refer to
CHAPTER 7
, of this
manual.