50
www.honeywell.com
Configuring via the Web Server
Configuring the Doors
Steps
: Use the descriptions in
Table 2-8
to configure each individual lock or Reader
LED:
Table 2-8:
Configuration > Doors: > 1 > Outputs Tab > Reader LED Dialog Box
Fields
Setting
Description
Name
Enter a unique name to identify the device.
Pulse Time
Specifies the duration for which the device will assume abnormal
status. For example, it specifies how long a horn will sound or a door
strike will remain released. The maximum number of hours is 1.
When the hour field is blank, the maximum number of minutes is 59.
When 1 is entered in the hour field, the maximum number of minutes
is 45 and the maximum number of seconds is 59.9. The sum of all
three units comprises the pulse time. Note that you can express
seconds in tenths of a second.
Time Zones
Specifies two schedules:
•
Energized
– sets the period during which the output is
automatically energized.
•
Disable Interlock
– sets the period during which the interlock, a
programmed interaction between selected inputs and outputs,
will be disabled. During the selected Time Zone this point
ignores all interlock actions to it, effectively disabling it from
being a Reacting Component during the Time Zone. Outside of
the Time Zone the point will react to interlocks as expected.
Latching
Toggles the state of the outputs between energized and de-energized
status upon every activation (code use, interlock, or manual pulse).
Interlock
Enables you to disable the interlock, or programmed interaction
between two points. When enabled, this point ignores all interlock
actions to it, effectively disabling it from being a Reacting
Component.
TZ Card Toggle
Requires, like the First Card Rule, a valid card read within the time
zone to enable the time zone (period in which doors are unlocked) to
take effect. Unlike the First Card Rule, however, the user can swipe
the card a second time to return the doors to a locked state. Note that
both TZ Card Toggle and First Card Rule cannot be enabled at the
same time. Appears only when the Lock option is selected.
First Card Rule
Requires a valid card read within the time zone to enable the time
zone (period in which doors are unlocked) to take effect. Note that
both TZ Card Toggle and First Card Rule cannot be enabled at the
same time. Appears only when the Lock option is selected.
Содержание NetAXS-123
Страница 6: ...vi www honeywell com ...
Страница 10: ...NetAXS 123 Access Control Unit User s Guide Document 800 05168 Revision B x ...
Страница 112: ...102 www honeywell com Using WIN PAK with NetAXS 123 Standalone Commands ...
Страница 128: ...118 www honeywell com Monitoring NetAXS 123 Status Monitoring System Status ...
Страница 138: ...128 www honeywell com File Management Generating Reports ...
Страница 162: ...152 www honeywell com Clearing the Cache ...
Страница 166: ...156 www honeywell com ...
Страница 170: ...Index W 160 www honeywell com Door 1 81 Door 2 86 Door 3 91 I O Settings 80 setup 80 standalone commands 96 ...