4. Set Up and Calibration Procedures - Maintenance Set Up Group
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
53
7/07
Maintenance Set Up Group
The Maintenance set up group consists of information about actuator operation accumulated through time.
This information (or maintenance statistics) can be used to evaluate actuator operation and determine
predicted or scheduled maintenance periods. Table 20 lists the parameters and selections available for the
SET MAINTENANCE group.
Please note that maintenance statistics are written to the EEPROM every 8 hours. Therefore the statistics
are saved in the event of a power interruption.
Table 20 Maintenance Set Up Group Parameters
Lower Display
Prompt
Upper Display
Selections or
Range of Setting
Parameter Definition
TEMP
nnnn F *
ACTUATOR TEMPERATURE
—
Read Only.
Displays the
current internal temperature of the actuator.
TEMPHI
nnnn F *
HIGH TEMPERATURE LIMIT
—Displays the high
temperature limit of the internal actuator temperature since it
was last reset.
TEMPLO
nnnn F *
LOW TEMPERATURE LIMIT
—Displays the low
temperature limit of the internal actuator temperature since it
was last reset.
hh:mm:ss
†
ACST
†
ACCUMULATED STALL TIME
—Displays the accumulated
stall time of the actuator motor since it was last reset.
STARTS
nnnn
ACCUMULATED MOTOR STARTS
—Displays the
accumulated motor starts since it was last reset.
RLnCNT
n
= 1, 2, 3 or 4
nnnn
RELAY CYCLE COUNTS
—Displays the accumulated cycle
counts of a relay since it was last reset. One relay cycle is
when a relay is energized and deenergized.
REGNn
nx
= 0 to 9
nnnn
ACCUMULATED MOTOR STARTS
—Displays the
accumulated motor starts in the 1
st
10% of motor span since
it was last reset. See “
Regions of Motor Travel
” in Section 5
TOTDEG
nnnn
TOTAL DEGREES OF MOTOR TRAVEL
—Displays the
total number of degrees of motor travel since it was last
reset.
DATSAV
DIS
ENAB
MAINTENANCE DATA FORCED SAVE
— Allows you to
manually force a save of the current maintenance data
values.
DISABLE
— Forced data save is disabled.
ENABLE
— Forced data save is enabled.
PASSWRD
nnnn
PASSWORD
—4-digit password is required to enable
maintenance reset function.
NOTE: Password is set (or changed) from the Lock set up
group.