Test Power Distribution PWA
Replace CPU
assembly.
Is correct
voltage present
at test points?
See below.
Remove extended
cover of actuator.
Are fuses good?
Replace fuses with
same type and
rating
Yes
D
Check Fuses F1
and F2 on the
power distribution
PWA.
No
Yes
No
Replace Power
Distribution PWA.
Figure 36 Test Power Distribution PWA
Power Distribution PWA Test Points
Connector
Test Points - Pins
Voltage
J2
Pin 1 to pin 7
5 V
J3
Pins 1,2 to pins 3, 4, 8
Pins 3, 4 to pin 7
5 V
9 V
J1
Pins 5, 6 to pins 7, 8
Pins 1, 2 to pins 7, 8
24 V
28 V + or – 3V