4. Set Up and Calibration Procedures - Calibration
58
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
Revision 5
7/07
Calibration Set up
Follow the steps below to set up the test equipment and actuator to verify calibration or perform calibration
procedures.
Step
Action
1
Connect the copper leads from the signal source to the input terminals of the actuator as
shown in Figure 17 or Figure 18.
2
Place signal source output to low end of input signal and switch power on.
3
Skip this step for slidewire emulation.
Connect a 250-ohm resistor across the Output terminals
of the actuator and connect the DVM leads to the terminals.
Input
28 29
-
+
Output
30 31
-
+
250 ohm resistor
needed for current
signal source
+
-
Calibrated
Signal
Source
+ -
250 ohm resistor
(supplied)
Digital
Voltmeter
Actuator
Figure 17 Calibration Wiring Connections (except slidewire emulation)