4. Set Up and Calibration Procedures - Lock Set Up Group
48
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
Revision 5
7/07
Set/Change Password
A password is required to enable and disable lockout features of the actuator. Lock out of calibration
information and other supervisory functions are controlled using the password. The password can be any
number from 0 to 4095. The password is set and/or changed by using the keys on the kepad and the local
display. Follow the steps below to change the password.
NOTE: The LOCK parameter must be set to NONE in order to change the password.
Step
Action
1
Press SET UP key until the display reads SET LOCK.
2
Press the FUNCTION key until the lower display reads LOCKID.
3
The upper display will show 0 (zero). Use the
or
keys to increment the number to the
correct password. The default password can also be used. See NOTE below.
4
Press the FUNCTION key so that the lower display reads LOCK.
5
Use the
or
keys so that display reads NONE and LOCK.
If the LOCK parameter is not set to NONE, a password must be entered to change the
parameter.
6
Press the FUNCTION key until the lower display reads LOCKID.
7
The upper display will show 0 (zero). Use the
or
keys to increment the number to the
new password. See NOTE below.
8
Press FUNCTION key to view next parameter, or press DISPLAY to exit set up mode.
Password is now set to new value.
NOTE:
When changing the value of the number, you can adjust a more significant digit in the upper
display by holding in one key
or
and pressing the other
or
at the same time.
The adjustment will move one digit to the left.
Press the key again and you will move one more digit to the left.