4. Set Up and Calibration Procedures - Setting End-of-Travel Limit Switches (actuators mfd. after 1/1/03)
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
69
7/07
•
Rotate the #2 limit switch operating cam to activate at this position. The switch roller arm should
go from being in an up, not depressed state, to a depressed state as the cam is rotated in the
direction of the shaft rotation going toward the limit position. This will cause the switch to go
from NC to NO and turn off the power to the motor when the switch activates. Both the NC and
NO contact states are available to the customer at the terminals (see Figure 13 page 26).
•
If optional auxiliary switches were ordered, these switches may also be set at this time. (See page
73 for details of setting auxiliary switches.)
3.
No additional adjustments are required.
4.
Double check limit switch actuation by first manually driving the actuator to each end of travel and
hearing the switch click or by detecting it with a continuity tester. Secondly, drive the actuator to both
ends of travel (using the auto/manual switch or by providing minimum and full input signal) and make
sure the switches activate and turn off the motor.