3. Installation - Electrical Installation
22
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
Revision 5
7/07
Electrical Installation
General Wiring Recommendations
WARNING
Only qualified personnel should perform wiring.
Wiring must conform to national and local electrical codes.
In general, stranded copper wire should be used. Unless locally applicable codes dictate otherwise, the
recommended minimum wire sizes in Table 2 should be observed.
Table 2 Recommended Minimum Wire Size
Gage No.
Description
14
Earth ground wire to common power supply.
18
Earth ground wire to single actuator. 120/240 V ac line leads. +24 V and common
signal leads.
Safety Precautions
WARNING
An external disconnect switch must be installed to break all current carrying conductors
connected to the actuator. Turn off power before working on conductors. Failure to observe
this precaution may result in serious personal injury.
Actuator Connections
WARNING
The ground terminal must be connected to a reliable earth ground.
WARNING
While the unit is powered, a potentially lethal shock hazard exists inside the case. Do not open
the case while the unit is powered. Do not access the terminals while the unit is powered.
The 10260S actuator terminal connections for the field wiring are located behind the cover on the actuator
case as shown in Figure 2. Power and field wiring is brought into the actuator through two access holes
located on the side of the actuator case. The screw terminals for all customer connections are identified in
Table 3.
Figure 13 shows the location of the terminal connections on the actuator terminal blocks. Desciptions for
power input, input and output signal connections are given in Table 3.