4. Set Up and Calibration Procedures - Current Out Set Up Group
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
43
7/07
Relay Type – Motor Starts
Selecting relay type STRT will cause the relay to trip when the number of motor starts exceeds the selected
limit. The motor starts value is stored as one of the maintenance group statistics. This example sets the
motor starts limit at 200,000 for Relay 1.
Set Up Group
Parameter
Value
SET RELAY1
RTYP11
STRT
R11 E
9
X10K
R11VAL
20
R11HL
HI
RTYP12
NONE
The resulting action is that Relay 1 will trip when the number of accumulated motor starts in the
maintenance group exceeds 200,000.
Current Out Set Up Group
Table 13 lists the parameters and selections available for the SET CUROUT group.
ATTENTION
If you change the output signal range of the actuator, you must perform an output calibration.
See
Calibrating Output, page 62
.
When selecting the output range of the actuator, the 4 – 20 mA selection is factory calibrated, therefore no
calibration is necessary. If you change the CUROUT selection, you must perform an output calibration so
that the values at the actuator output terminals agree with the CUROUT selection.
Additionally, if you change the CUROUT selection back to 4 – 20 mA from another selection, you must
either perform an output calibration or perform a LD CAL function to the output (COUT) to restore the
factory calibration values to the 4 – to 20 mA selection. The LD CAL function is in the INPUT set up
group.
Table 13 Current Out Set Up Group Parameters
Lower Display
Prompt
Upper Display
Selections
Parameter Definition
CUROUT
Note
: If output
type from model
selection guide
is:
0/4-20mA, 0/1-
5Vdc
4 – 20
0 – 20
1 – 5V
0 – 5V
OUTPUT SIGNAL RANGE
—Selects the signal output
range.
4 to 20 mA
0 to 20 mA
1 to 5 Volts
0 to 5 Volts