4. Set Up and Calibration Procedures - Read Status Set Up Group
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
49
7/07
Read Status Set Up Group
Table 18 lists the parameters and selections available for the READ STATUS group.
Table 18 Read Status Set Up Group Parameters
Lower Display
Prompt
Upper Display
Selections or
Range of Setting
Parameter Definition
FAILSF
NO
YES
FAILSAFE
—
Read Only.
Shows whether actuator in failsafe.
No
—Actuator not in failsafe.
Yes
—Actuator in failsafe, see Troubleshooting section
RAMTST
PASS
FAIL
RAM TEST DIAGNOSTIC
—
Read Only.
Shows status of
RAM test diagnostic.
Pass
—Test passed, no errors
Fail
—Test failed, see Troubleshooting section.
SEETST
PASS
FAIL
SERIAL EEPROM TEST DIAGNOSTIC
—
Read Only.
Shows status of serial electrically eraseable PROM test
diagnostic.
Pass
—Test passed, no errors
Fail
—Test failed, see Troubleshooting section.
CFGTST
PASS
FAIL
CONFIGURATION TEST DIAGNOSTIC
—
Read Only.
Shows status of Configuration test diagnostic.
Pass
—Test passed, no errors
Fail
—Test failed, see Troubleshooting section.
CALTST
PASS
FAIL
CALIBRATION TEST DIAGNOSTIC
—
Read Only.
Shows
status of Calibration test diagnostic.
Pass
—Test passed, no errors
Fail
—Test failed, see Troubleshooting section.