ENGINEERING MANUAL OF AUTOMATIC CONTROL
CHILLER, BOILER, AND DISTRIBUTION SYSTEM CONTROL APPLICATIONS
364
With both valves operating, as the total demand drops below
the capacity of the large valve for five minutes, the small valve
shall close. With the large valve operating, as the demand drops
below the capacity of the small valve for five minutes, the large
valve shall close and the small valve shall assume the load.
Demand Limiting:
A large valve Kv limiting parameter shall be provided and
set such that upon full demand, the valve Kv shall not exceed
the design Kv of 51.
All valve timings and parameters shall be field adjustable by
the owner.
THREE-WAY VALVE
The supply water temperature to the radiators (Fig. 96) is
reset by the controller modulating the three-way valve. The
controller modulates the three-way valve to maintain the reset
schedule in response to temperature changes at the outdoor air
sensor and the supply water sensor. Pump runs continuously
during the heating season. As water temperature changes, the
heat output changes linearly. This allows accurate changes in
heating plant capacity as a function of outdoor air temperature
or some other signal to match the load.
Hot Water Control Method Selection
Supply water temperature control is suitable for controlling the
heat delivery from a heat exchanger or a secondary water pump.
Flow control is acceptable for controlling individual terminal
units such as convectors, fan coils, or induction units. An equal
percentage characteristic valve complements the water to air
heat exchanger characteristic of heat output versus flow. The
result is a relatively linear heat output as a function of stem
position (Fig. 97). The heat output is relatively constant,
providing optimized controllability of heat exchangers such as
converters, fan coils, and induction units.
Fig. 96. Radiators with Scheduled Water
Temperature Using Three-Way Valve.
Coordinating Valve Selection and System Design
A prerequisite to good modulating control of water systems
is a coordinated design of the entire water system. All control
valves must be sized so that the system will deliver design flow
at full load and not generate uncontrollable conditions at
minimum load.
Control valve selection is based on pressure differentials at
the valve location, full load flow conditions, valve close-off,
and valve controllability at minimum load conditions.
Generally, for smooth modulating control, the no-flow
pressure differential should not exceed the full flow differential
by more than 50 percent.
C2917
3-WAY
VALVE
MINIMUM
BOILER
FLOW (BYPASS)
BOILER
TO OTHER
RADIATORS
SUPPLY WATER
SENSOR
CONTROLLER
OUTDOOR
AIR
SENSOR
Fig. 97. Control of a Water Heat Exchanger Using an
Equal Percentage Characteristic Valve.
CHILLED WATER DISTRIBUTION SYSTEMS
GENERAL
Chilled water systems for cooling of commercial buildings
usually provide water between 5
°
C and 10
°
C to finned coils in
room units or air handlers.
The amount of water delivered to the cooling coils and/or
produced by chillers is related to temperature difference (
∆
t)
across the coil or chiller and energy (kilowatts of refrigeration)
by the equation:
C2918
HEA
T
EXCHANGER
OUTPUT
VALVE POSITION
W
A
TER FLO
W
CL
OP
VALVE POSITION
CL
OP
Where:
Q = Volume flow rate (L/s)
h
= Cooling rate
∆
t
= water temperature difference in kelvins
4.2 = a constant
EXAMPLE:
Given: A 3.52 kW chiller with a
∆
t of 6 kelvins.
Q =
h
4.2 x
∆
tW
Q =
3.52 kW
4.2 x 6
= 0.14 L/s
Содержание AUTOMATIC CONTROL SI Edition
Страница 1: ...AUTOMATIC CONTROL for ENGINEERING MANUAL of COMMERCIAL BUILDINGS SI Edition ...
Страница 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Страница 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Страница 11: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 1 CONTROL SYSTEM FUNDAMENTALS ...
Страница 12: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 2 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Страница 66: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL PSYCHROMETRIC CHART FUNDAMENTALS 56 ...
Страница 128: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Страница 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Страница 208: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 198 ...
Страница 209: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 199 CONTROL SYSTEM APPLICATIONS ...
Страница 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 200 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 435: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 425 ENGINEERING INFORMATION ...
Страница 436: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 426 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 493: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 483 INDEX ...
Страница 506: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 496 NOTES ...
Страница 507: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 497 NOTES ...
Страница 508: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 498 NOTES ...
Страница 509: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 499 NOTES ...
Страница 510: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 500 NOTES ...
Страница 511: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 501 NOTES ...
Страница 512: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 502 NOTES ...