ENGINEERING MANUAL OF AUTOMATIC CONTROL
PNEUMATIC CONTROL FUNDAMENTALS
74
Figure 25 shows a typical application of a thermostat and
velocity controller on a Variable Air Volume (VAV) terminal
unit with hot water reheat. The thermostat senses a change in
room temperature and resets the velocity setpoint of the velocity
controller. The controller repositions the VAV damper to
increase or decrease airflow accordingly. If a change in duct
static pressure modifies the flow, the controller repositions the
actuator to maintain the correct flow. The reheat valve operates
only when the thermostat has reset the velocity setpoint down
to minimum airflow and the thermostat calls for heating.
M
VELOCITY
SENSOR IN
DUCTWORK
VAV BOX
DAMPER
DAMPER
ACTUATOR
VELOCITY
CONTROLLER
VAV BOX
REHEAT VALVE
ROOM
THERMOSTAT
M10296
Fig. 25. VAV Box Velocity Controller Control System.
ACTUATORS AND FINAL CONTROL ELEMENTS
A pneumatic actuator and final control element such as a valve
(Fig. 26) or damper (Fig. 27) work together to vary the flow of
the medium passing through the valve or damper. In the actuator,
a diaphragm and return spring move the damper push rod or valve
stem in response to changes in branchline pressure.
Fig. 26. Pneumatic Actuator and Valve.
C2611
DAMPER
AIRFLOW
PUSH
ROD
DAMPER
ACTUATOR
SPRING
PISTON
ROLLING
DIAPHRAGM
BRANCH
LINE
Fig. 27. Pneumatic Actuator and Damper.
ACTUATORS
GENERAL
Pneumatic actuators position damper blades and valve
stems. A damper actuator typically mounts on ductwork or on
the damper frame and uses a push rod and crank arm to position
the damper blades (rotary action). A valve actuator mounts on
the valve body and positions the valve stem directly (linear
action) for a globe valve or rotary action via linkage for a
butterfly valve. Valve actuator strokes typically are between 6
and 38 millimeters. Damper actuator strokes range from one
to four inches (longer in special applications). In commercial
pneumatic actuators, air pressure positions the actuator in one
direction and a spring returns it the other direction.
Valve actuators are direct or reverse acting. Damper actuators
are direct acting only. A direct-acting actuator extends on an
increase in branchline pressure and retracts on a decrease in
pressure. A reverse-acting actuator retracts on an increase in
branchline pressure and extends on a decrease in pressure.
Pneumatic valve and damper actuator assemblies are termed
“normally open” or “normally closed.” The normal position is
the one assumed upon zero actuator air pressure. Three-way valves
have both normally open (N.O.) and normally closed (N.C.) ports.
SPRING RANGES
Springs used in valve and damper actuators determine the
start pressure and pressure change required for full movement
of the actuator from open to closed, or from closed to open.
BRANCH
LINE
SPRING
VALVE
STEM
INLET
FLOW
OUTLET
FLOW
DIAPHRAGM
VALVE
ACTUATOR
VALVE
M10361
Содержание AUTOMATIC CONTROL SI Edition
Страница 1: ...AUTOMATIC CONTROL for ENGINEERING MANUAL of COMMERCIAL BUILDINGS SI Edition ...
Страница 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Страница 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Страница 11: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 1 CONTROL SYSTEM FUNDAMENTALS ...
Страница 12: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 2 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Страница 66: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL PSYCHROMETRIC CHART FUNDAMENTALS 56 ...
Страница 128: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Страница 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Страница 208: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 198 ...
Страница 209: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 199 CONTROL SYSTEM APPLICATIONS ...
Страница 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 200 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 435: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 425 ENGINEERING INFORMATION ...
Страница 436: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 426 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 493: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 483 INDEX ...
Страница 506: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 496 NOTES ...
Страница 507: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 497 NOTES ...
Страница 508: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 498 NOTES ...
Страница 509: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 499 NOTES ...
Страница 510: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 500 NOTES ...
Страница 511: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 501 NOTES ...
Страница 512: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 502 NOTES ...