ENGINEERING MANUAL OF AUTOMATIC CONTROL
CONTROL FUNDAMENTALS
24
Reset error correction time is proportional to the deviation
of the controlled variable. For example, a four-percent deviation
from the setpoint causes a continuous shift of the proportional
band at twice the rate of shift for a two-percent deviation. Reset
is also proportional to the duration of the deviation. Reset
accumulates as long as there is offset, but ceases as soon as the
controlled variable returns to the setpoint.
With the PI controller, therefore, the position of the final
control element depends not only upon the location of the
controlled variable within the proportional band (proportional
band adjustment) but also upon the duration and magnitude of
the deviation of the controlled variable from the setpoint (reset
time adjustment). Under steady state conditions, the control
point and setpoint are the same for any load conditions, as shown
in Figure 37.
PI control adds a component to the proportional control
algorithm and is described mathematically by:
Where:
V = output signal
K = proportionality constant (gain)
E
= deviation (control point - setpoint)
T
1
= reset time
K/T
1
= reset gain
dt = differential of time (increment in time)
M = value of the output when the deviation
is zero
Integral windup, or an excessive overshoot condition, can
occur in PI control. Integral windup is caused by the integral
function making a continued correction while waiting for
feedback on the effects of its correction. While integral action
keeps the control point at setpoint during steady state conditions,
large overshoots are possible at start-up or during system upsets
(e.g., setpoint changes or large load changes). On many systems,
short reset times also cause overshoot.
Integral windup may occur with one of the following:
— When the system is off.
— When the heating or cooling medium fails or is not
available.
— When one control loop overrides or limits another.
Integral windup can be avoided and its effects diminished.
At start-up, some systems disable integral action until measured
variables are within their respective proportional bands. Systems
often provide integral limits to reduce windup due to load
changes. The integral limits define the extent to which integral
action can adjust a device (the percent of full travel). The limit
is typically set at 50 percent.
The reset action of the integral component shifts the
proportional band as necessary around the setpoint as the load
on the system changes. The graph in Figure 36 shows the shift
of the proportional band of a PI controller controlling a normally
open heating valve. The shifting of the proportional band keeps
the control point at setpoint by making further corrections in
the control signal. Because offset is eliminated, the proportional
band is usually set fairly wide to ensure system stability under
all operating conditions.
T1
T2
T3
T4
CLOSED
VALVE
POSITION
OPEN
SETPOINT
TIME
C2098
DEVIATION
FROM
SETPOINT
INTEGRAL ACTION
CONTROL POINT (LOAD CHANGES)
PROPORTIONAL CORRECTION
Fig. 36. Proportional Band Shift Due to Offset.
Reset of the control point is not instantaneous. Whenever
the load changes, the controlled variable changes, producing
an offset. The proportional control makes an immediate
correction, which usually still leaves an offset. The integral
function of the controller then makes control corrections over
time to bring the control point back to setpoint (Fig. 37). In
addition to a proportional band adjustment, the PI controller
also has a reset time adjustment that determines the rate at which
the proportional band shifts when the controlled variable
deviates any given amount from the setpoint.
Fig. 37. Proportional-Integral Control
Response to Load Changes.
V = KE +
K
T
1
∫
Edt + M
Integral
34
37
40
43
46
CLOSED
50% OPEN
100% OPEN
SETPOINT (
°
C)
PROPORTIONAL BAND
FOR SEPARATE LOAD
CONDITIONS
HEATING
VALVE
POSITION
0%
LOAD
50%
LOAD
100%
LOAD
= CONTROL POINT
THROTTLING RANGE = 5 KELVINS
C3985
Содержание AUTOMATIC CONTROL SI Edition
Страница 1: ...AUTOMATIC CONTROL for ENGINEERING MANUAL of COMMERCIAL BUILDINGS SI Edition ...
Страница 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Страница 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Страница 11: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 1 CONTROL SYSTEM FUNDAMENTALS ...
Страница 12: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 2 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Страница 66: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL PSYCHROMETRIC CHART FUNDAMENTALS 56 ...
Страница 128: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Страница 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Страница 208: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 198 ...
Страница 209: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 199 CONTROL SYSTEM APPLICATIONS ...
Страница 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 200 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 435: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 425 ENGINEERING INFORMATION ...
Страница 436: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 426 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 493: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 483 INDEX ...
Страница 506: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 496 NOTES ...
Страница 507: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 497 NOTES ...
Страница 508: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 498 NOTES ...
Страница 509: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 499 NOTES ...
Страница 510: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 500 NOTES ...
Страница 511: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 501 NOTES ...
Страница 512: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 502 NOTES ...