ENGINEERING MANUAL OF AUTOMATIC CONTROL
CHILLER, BOILER, AND DISTRIBUTION SYSTEM CONTROL APPLICATIONS
351
The greatest change at the sensor provides the most tolerant
and robust control. For this reason the sensor is located, not
across the chiller with a setpoint of 27.9 kPa, but across Coil 1
where the greatest differential pressure change exists (84 kPa
at design to 103.5 kPa at 90 percent of design).
NOTE: With the controller pickups in these locations, it does
not matter where in the system the load is located, what
value it has, or whether it is symmetrical or non-
symmetrical.
Also note that the Load 1 balancing valve takes a full flow
36 kPa drop and even with the pressure bypass valve, the control
valves will be subjected to drops of near 103.5 kPa for light
loads. For larger and more extended systems, both of these
values must be considered when evaluating reverse return and
control valve high differential pressure solutions.
These values lead to the conclusion that a differential pressure
bypass solution may satisfy the light-load flow through a chiller,
but may not adequately relieve control valve light-load
differential pressures on larger systems. Also be aware that
pressure drop changes due to scaled chiller tubes effect the
bypass valve operation.
Single Pump, Pressure Bypass, Reverse Return
A reverse return system analysis equivalent to the direct return
analysis of Figure 74 would show that at half flow and no
bypass, the pump pressure still rises to 162 kPa and the control
valve drop still rises to 132 kPa.
For 90 percent flow control, the pump still operates at 150 kPa
with the sensor located as far away from the pump as practical to
take advantage of as many friction drop changes as possible.
The preferred sensor location (Fig. 76) is DP-1 if point A is
near Load 1. Sensor location DP-2 is second best and again if
point B is near Load 1. If location DP-3 is selected by default,
with a setpoint of 122.1 kPa as compared with the DP-3 full
flow differential pressure of 107 kPa. This small 15.1 kPa
change requires a higher quality sensor and more frequent
calibration checks than for locations DP-1 and DP-2. Locate
the pressure bypass valve and sensor as far from the chiller/
pump as possible , but no closer than DP-3.
In all cases it is still preferable to locate the system strainer
outside the control loop as shown in Figure 75.
Fig. 76. Single Pump, Pressure Bypass, Reverse Return at 90 percent Flow.
CHILLER
27.9 kPa
DROP
9.3 kPa DROP
HEAT/
COOL
COIL
1
V1
HEAT/
COOL
COIL
2
V2
HEAT/
COOL
COIL
3
V3
HEAT/
COOL
COIL
4
V4
HEAT/
COOL
COIL
5
V5
HEAT/
COOL
COIL
6
V6
PUMP
66 L/s
150 kPa
9.3 kPa DROP
11 L/s
PER
AHU COIL
DP2
DP1
POINT B
DP3
RETURN
POINT A
SUPPLY
SYSTEM WITH 90% FLOW THROUGH COIL
M15288
Содержание AUTOMATIC CONTROL SI Edition
Страница 1: ...AUTOMATIC CONTROL for ENGINEERING MANUAL of COMMERCIAL BUILDINGS SI Edition ...
Страница 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Страница 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Страница 11: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 1 CONTROL SYSTEM FUNDAMENTALS ...
Страница 12: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 2 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Страница 66: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL PSYCHROMETRIC CHART FUNDAMENTALS 56 ...
Страница 128: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Страница 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Страница 208: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 198 ...
Страница 209: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 199 CONTROL SYSTEM APPLICATIONS ...
Страница 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 200 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 435: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 425 ENGINEERING INFORMATION ...
Страница 436: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 426 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 493: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 483 INDEX ...
Страница 506: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 496 NOTES ...
Страница 507: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 497 NOTES ...
Страница 508: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 498 NOTES ...
Страница 509: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 499 NOTES ...
Страница 510: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 500 NOTES ...
Страница 511: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 501 NOTES ...
Страница 512: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 502 NOTES ...