ENGINEERING MANUAL OF AUTOMATIC CONTROL
DAMPER SELECTION AND SIZING
452
M10418
DAMPER
BAFFLE
Fig. 16. Baffle Inside Duct Surrounds Damper.
TYPICAL DAMPER CONSTRUCTION
Figure 17 shows construction of an opposed blade damper
with linkage. A parallel blade damper is essentially identical
except for placement of blade linkage and rotation direction of
alternate blades. Higher leakage dampers have either no blade
side seals or less effective sealing elements, e.g., adhesive-
backed cellular foam strips.
PERFORMANCE DATA
Performance data for dampers can vary in content and form
due to the many types of dampers and the philosophies of their
manufacturers. When casually compared, performance ratings
of different dampers may seem equivalent but are not due to
differences in criteria on which the data is based. The following
paragraphs discuss the types of performance data and their
variations.
LEAKAGE RATINGS
Leakage ratings of dampers are the most widely publicized
damper performance data. Figure 18 graphically shows typical
leakage performance of dampers with side seals, but without
blade edge seals. The torque necessary to achieve the indicated
leakage ratings is specified at the top of the graph as 6.0 Nm
per square meter of damper area. The wide performance band
is explained by the note at the bottom of the graph.
For typical dampers, leakage increases more significantly with
the number of blades than with the length of the blades. The data
shown applies to a combination of damper heights and widths.
For example, a damper 1.22m high x 0.305m wide is the area
equivalent of a damper 0.305m. high x 1.22m wide. However,
there is significantly more leakage with the 1.2m high x 0.305m
wide damper, due to the increased number of blades. Using the
leakage performance graph in Figure 18, the range of leakage for
these two dampers (0.37 m
2
each) at 0.249 kPa is:
Leakage = Area x Rating/m
2
Minimum Leakage = 0.37 x 0.05 (min)
= 0.018 m
3
/s
Maximum Leakage
= 0.37 x 0.13 (max)
= 0.47 m
3
/s
Performance characteristics for low leakage dampers differ
from standard dampers. Figure 19 shows typical pressure drop/
leakage rating relationship for low leakage dampers. Specific
leakage ratings for horizontal (A) and vertical (B) damper
dimensions are listed and the torque required has been increased
to a flat value for any single section to accommodate light
compression blade edge seals.
Using the leakage ratings in Figure 19, the leakage of the
two dampers in the previous example at 0.249 kPa is:
0.305m (A) + 1.22m (B) = 0.95 L/s + 20.5 L/s
= 21.45 L/s
If the A and B dimensions are reversed, the leakage is as
follows:
1.22m (A) + 0.305m (B) = 3.4 L/s + 6 L/s
= 9.4 L/s
Other methods of conveying leakage ratings are a tabular
format (e.g., leakage per area in m
3
/s per square meter) and a
percentage basis. The tabular format lists specific ratings for
each individual damper size. Leakage per area must include
sizes of interest. The percentage basis leakage rating is
meaningless unless complete conditions including total airflow
that the data is based on are also stated.
In many cases, damper data indicates that it is certified by an
industry association. Certification means that tests were done
under conditions defined by an association of manufacturers
but is not a rating by an approval body. For applications other
than smoke and fire, there are no approval bodies governing
damper leakage or any other performance characteristics.
Содержание AUTOMATIC CONTROL SI Edition
Страница 1: ...AUTOMATIC CONTROL for ENGINEERING MANUAL of COMMERCIAL BUILDINGS SI Edition ...
Страница 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Страница 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Страница 11: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 1 CONTROL SYSTEM FUNDAMENTALS ...
Страница 12: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 2 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Страница 66: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL PSYCHROMETRIC CHART FUNDAMENTALS 56 ...
Страница 128: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Страница 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Страница 208: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 198 ...
Страница 209: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 199 CONTROL SYSTEM APPLICATIONS ...
Страница 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 200 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 435: ...SMOKE MANAGEMENT FUNDAMENTALS ENGINEERING MANUAL OF AUTOMATIC CONTROL 425 ENGINEERING INFORMATION ...
Страница 436: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL SMOKE MANAGEMENT FUNDAMENTALS 426 SMOKE MANAGEMENT FUNDAMENTALS ...
Страница 493: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 483 INDEX ...
Страница 506: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 496 NOTES ...
Страница 507: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 497 NOTES ...
Страница 508: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 498 NOTES ...
Страница 509: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 499 NOTES ...
Страница 510: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 500 NOTES ...
Страница 511: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 501 NOTES ...
Страница 512: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 502 NOTES ...