SJ100DN Inverter
73
Error Responses to Set_Attribute_Single
– In certain conditions the inverter cannot
Set an attribute as the host has requested. For example, the host’s data might be out-of-
range for the specified parameter. The inverter will return an error code, listed for the
specific condition in the table below.
NOTE:
The Message Router Object (Class ID = 2 hex) is supported, but has no setting.
Error Condition
Type
Type
code
Specific
error code
The inverter is in Run Mode
Device state conflict
10h
00
A trip, undervoltage, or trip-retry exists
01
Software lock mode enabled
02
Executing auto-tuning
04
Value less than start frequency setting
Invalid parameter
(check F_01, A_03,
A203, A_20–A_35,
A220, A_38, A_52,
A_61, A_62)
20h
00
Value less than lower frequency limit setting
01
Value more than upper frequency limit setting
02
Value more than maximum frequency setting
03
Out-of-range condition not listed above
Invalid parameter
04
DeviceNet Object (Class ID = 3 hex)
Category
Attribute
ID
Access
Rule
Data Type
Initialization
Class
Revision
1
Get
UINT
2
Instance 1
MAC ID
1
Get/Set
USINT
63
Baud rate
2
Get/Set
USINT
125k bits/sec.
BOI
3
Get
BOOL
0
Bus OFF counter
4
Get/Set
USINT
0
Allocation information choice
byte
5
Get
BYTE
—
Master’s MAC ID
—
—
USINT
—
Supported Services, DeviceNet Object
Service Name
Code
Description
Get_Attribute_Single
0Eh
Set_Attribute_Single
10h
Allocate_M/S_Connection_Set
4Bh
Release_M/S_Connection_Set
4Ch