SJ100DN Inverter
85
B212 Level of electronic thermal
setting, 2nd motor
2
112
2
5% to 120% rated
current, in A
10
G/S
B_13 Electronic thermal characteristic
1
113
1
0 Reduced torque
1 Constant torque
2 Reduced
torque2
—
G/S
B213 Electronic thermal characteristic,
2nd motor
2
113
1
0 Reduced torque
1 Constant torque
2 Reduced
torque2
—
G/S
B_21 Overload restriction operation
mode
1
121
1
0 Disabled
1 Enabled for
acceleration and
constant speed
2 Enabled for
constant speed
only
—
G/S
B_22 Overload restriction setting
1
122
2
50% to 150%
rated current, in A
100
G/S
B_23 Deceleration rate at overload
restriction
1
123
2
0.3 – 30.0
10
G/S
B_31 Software lock mode selection
1
131
1
0 all parameters
except B_31 are
locked if [SFT] is
ON
1 all parameters
except B_31 and
output freq. F_01
when [SFT] is ON
2 all parameters
except B_31 are
locked
3 all parameters
except B_31 and
F_01 are locked
—
G/S
B_82 Start frequency adjustment
1
182
2
0.5 – 9.9 Hz
100
G/S
B_83 Carrier frequency setting
1
183
1
0.5 – 16.0kHz
10
G/S
B_84 Initialization mode (parameters
or trip history)
1
184
1
0 Trip history
clear
1 Parameter
initialization
—
G/S
“B” Group Parameters
DeviceNet Class ID = 103
Func.
Code
Name
Inst Attr Size
Range
Scaling
Get/
Set
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com