Appendix B:
78
Appendix B:
Network Register Map
The following tables list the DeviceNet explicit addressing to access inverter parameters.
Each parameters address consists of Class ID, Instance, and Attribute. The host will also
need to use the Size (number of bytes) in the request. Most of the parameters provide
both Get and Set access (denoted by “G/S”) in the tables).
The inverter returns scalar values in decimal format. The scale factors are presented in
the Scaling column. To get a parameter’s actual value, the host computer will need to
divide the data by the scale factor (unless it is “1”). The result will be a decimal number
with an integer part and a decimal (fractional) part.
Main Profile Parameters and Basic Inverter Data
“D” Group Parameters and
Basic Inverter Data
DeviceNet Class ID = 100
Func.
Code
Name
Inst Attr Size
Range
Scaling
Get/
Set
—
Rated capacity
1
100
1
1 0.2 kW
2 0.4 kW
3 0.55 kW
4 0.75kW
5 1.1 kW
6 1.5 kW
7 2.2 kW
8 8.3 kW
9 3.7 kW
10 4.0 kW
11 5.5 kW
12 7.5 kW
—
Get
—
Input AC voltage class
1
101
1
1 200V
2 400V
—
Get
—
Rated output current
1
102
2
0.00 – 655.35A
100
Get
—
Inverter status
1
103
1
0 – 255
1
Get
D_01 Output frequency monitor
1
104
2
0.01 – 360.00Hz
100
Get
D_02 Output current monitor
1
105
2
0.00 – 655.35A
10
Get
D_03 Rotation direction monitor
1
106
1
1 forward
2 reverse
—
Get
D_05 Intelligent input terminal status
1
108
1
0 open
1 close,
Bit 0 = terminal 1
Bit 1 = terminal 2
Bit 2 = terminal 3
—
Get