SJ100DN Inverter
79
D_06 Intelligent output terminal status
1
109
1
0 open
1 close,
Bit 0 = terminal 11
Bit 1 = terminal 12
—
Get
D_07 Scaled output frequency monitor
1
110
4
0.00–35964.00Hz
(= 360 * 99.9)
100
Get
D_16 Cumulative operation RUN time
monitor
1
115
4
0 – FFFFFFh
(hex) hours
1
Get
—
P–N voltage monitor
1
118
2
0.0 – 6553.5V
10
Get
—
Rate of BRD loading
1
119
1
0 – 100%
1
Get
—
Rate of electronic thermal
loading
1
120
1
0 – 100%
1
Get
—
Trip count
1
121
1
0 – 255
1
Get
D_08 Trip event monitor (nth trip)
1
122
1
00 to 60 (see Ch.6
in manual)
—
Get
Output frequency at trip point
1
123
2
0.01 – 360Hz
100
Get
Motor current at trip point
1
124
2
0.00 – 655.35A
100
Get
DC bus voltage at trip point
1
125
2
0.0 – 6553.5V
10
Get
Cumulative operation RUN time
at trip point
1
126
4
0 – FFFFFFh
(hex) hours
1
Get
D_09 Trip event monitor (nth-1 trip)
1
128
1
00 to 60 (see Ch.6
in manual)
—
Get
Output frequency at trip point
1
129
2
0.01 – 360Hz
100
Get
Motor current at trip point
1
130
2
0.00 – 655.35A
100
Get
DC bus voltage at trip point
1
131
2
0.0 – 6553.5V
10
Get
Cumulative operation RUN time
at trip point
1
132
4
0 – FFFFFFh
(hex) hours
1
Get
D_09 Trip event monitor (nth-2 trip)
1
134
1
00 to 60 (see Ch.6
in manual)
—
Get
Output frequency at trip point
1
135
2
0.01 – 360Hz
100
Get
Motor current at trip point
1
136
2
0.00 – 655.35A
100
Get
DC bus voltage at trip point
1
137
2
0.0 – 6553.5V
10
Get
Cumulative operation RUN time
at trip point
1
138
4
0 – FFFFFFh
(hex) hours
1
Get
“D” Group Parameters and
Basic Inverter Data
DeviceNet Class ID = 100
Func.
Code
Name
Inst Attr Size
Range
Scaling
Get/
Set
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com