Configuring Drive Parameters
30
Intelligent Output Terminals
– The SJ100DN DeviceNet Series inverters have 5 of the
6 possible output option assignments for standard SJ100 inverters ([OD] is removed).
However, note that the alarm relay contact terminals [AL0], [AL1], and [AL2] are not
present on the SJ100DN DeviceNet Series inverters (so C_24 and C_33 are not present
on SJ100DN).
The output logic convention is programmable for terminals [11] and [12]. The open-
collector output terminals [11] and [12] default to normally open (active low), but you
can select normally closed (active high) for these terminals in order to invert the sense of
the logic.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–F
(Jpn)
Units
C_21 Terminal [11] function
Select function for terminal
[11],
5 options (see inverter manual
✘
00
[RUN]
00
[RUN]
00
[RUN]
—
C_22 Terminal [12] function
Select function for terminal
[12],
5 options (see inverter manual)
✘
05
[AL]
05
[AL]
05
[AL]
—
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–F
(Jpn)
Units
C_31 Terminal [11] active
state
Select logic convention, two
option codes:
00... normally open [NO]
01... normally closed [NC]
✘
00
00
00
—
C_32 Terminal [12] active
state
Select logic convention, two
option codes:
00... normally open [NO]
01... normally closed [NC]
✘
00
00
00
—