Configuring Drive Parameters
28
“C” Group: Intelligent Terminal Functions
Intelligent Input Terminals
– The three intelligent input terminals for SJ100DN
DeviceNet Series inverters have 22 possible option assignments.
NOTE:
Terminal [3] can operate as the PTC (thermistor thermal protection) input. Thus,
it has the additional [PTC] terminal input (option code 19) that may be assigned.
The input logic convention is programmable for each of the three inputs. The inputs
default to normally open (active high), but you can select normally closed (active low) in
order to invert the sense of the logic.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–F
(Jpn)
Units
C_01 Terminal [1] function
Select function for terminal [1]
22 options (see inverter
manual)
✘
00
[FW]
00
[FW]
00
[FW]
—
C_02 Terminal [2] function
Select function for terminal [2]
22 options (see inverter
manual)
✘
21
[STP]
21
[STP]
21
[STP]
—
C_03 Terminal [3] function
Select function for terminal [3]
23 options (see inverter manual
and Note below)
✘
12
[EXT]
12
[EXT]
12
[EXT]
—
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–F
(Jpn)
Units
C_11 Terminal [1] active state Select logic convention, two
option codes:
00... normally open [NO]
01... normally closed [NC]
✘
00
00
00
—
C_12 Terminal [2] active state Select logic convention, two
option codes:
00... normally open [NO]
01... normally closed [NC]
✘
00
00
00
—
C_13 Terminal [3] active state Select logic convention, two
option codes:
00... normally open [NO]
01... normally closed [NC]
✘
00
00
00
—