Inverter Mounting and Installation
22
Select the Keypad for the RUN Command
– The RUN command causes the inverter to
accelerate the motor to the selected speed. For local (non-network) inverter control, you
can program the inverter to respond to either the control terminal signal (default) or the
keypad RUN key. Follow the steps in the table below to select the front panel RUN key
as the source for the RUN Command (the table resumes action from the end of the
previous table).
NOTE:
When you press the STR key in the last step above (and the display = 02), the
Run Key Enable LED above the RUN key on the keypad will turn ON. This is normal,
and does not mean the motor is trying to run. It means that the RUN key is now enabled.
DO NOT press the RUN key at this time—finish out the programming exercise first.
Action
Display
Func./Parameter
Press the
key.
Run command source
Press the
key.
1 = control terminals (default)
2 = keypad
Press the
key.
2 = keypad (selected)
Press the
key.
Stores parameter, returns to “A”
Group list
2
A 0 2
FUNC.
0 1
1
0 2
STR
A 0 2