Operations and Monitoring
36
Use with DeviceNet operation
– When the SJ100DN inverter is under network control,
Run and Stop commands will typically arrive via the DeviceNet network. However, a
network communications interruption is possible at any time. So for safety reasons, it is
important to provide a dedicated Stop signal input as shown below.
In the graph below, the network FWD command places the inverter in Run mode. While
the motor is running, the local [STP] input terminal activates, causing the inverter to
decelerate the motor to a stop. It remains stopped even though the FW command is still
active. The FW command must turn OFF and ON again to resume motor operation.
Inverter
Network host
DeviceNet network
[STP]
Run/Stop commands
Output
Frequency
[STP]
Network FW command
t