Network Register Map
84
Fine Tuning Functions
A296 Dec1 to Dec2 frequency transi-
tion point, 2nd motor
2
196
2
0.0 – 360.0Hz
100
G/S
A_97 Acceleration curve selection
1
197
1
0 linear
1 S-curve
—
G/S
A_98 Deceleration curve selection
1
198
1
0 linear
1 S-curve
—
G/S
“A” Group Parameters
DeviceNet Class ID = 101
Func.
Code
Name
Inst Attr Size
Range
Scaling
Get/
Set
Supported Services, DeviceNet Class ID = 101
Service Name
Code
Description
Get_Attribute_Single
0Eh
Set_Attribute_Single
10h
“B” Group Parameters
DeviceNet Class ID = 103
Func.
Code
Name
Inst Attr Size
Range
Scaling
Get/
Set
B_01 Selection of automatic restart
mode
1
101
1
0 Alarm output
after trip, no
automatic restart
1 Restart at 0Hz
2 Resume opera-
tion after freq.
matching
3 Resume
previous freq. after
freq. matching,
then decelerate to
stop and display
trip info.
—
G/S
B_02 Allowable under-voltage power
failure time
1
102
2
0.3 – 25.0 sec.
10
G/S
B_03 Retry wait time before motor
restart
1
103
2
0.3 – 100.0 sec.
10
G/S
B_12 Level of electronic thermal
setting
1
112
2
5% to 120% rated
current, in A
10
G/S
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com