Network Control and Monitoring
68
The table below expands Byte 0 in the preceding table.
Inverter Produced Data, (Host) Input Instance (P_47) = 71
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Freq.
Arrival
Network
Refer-
ence
Network
Control
Ready
RV Run
FW Run
Warning
Trip
1
Inverter status (see status code table, next page)
2
Output frequency monitor (low byte), D_01 value
3
Output frequency monitor (high byte), D_01 value
Inverter Produced Data, Status Byte
Bit
Name
Bit = 0
Bit = 1
0
Trip
No faults exist
Trip exists, not cleared
1
Warning
No warning exists
Warning condition exists
2
FW Run
Inverter stopped or in RV
Inverter in FW Run
3
RV Run
Inverter stopped or in FW
Inverter in RV Run
4
Ready
Inverter is not ready
Inverter is ready
(status byte code = 3, 4, or 5)
5
Network Control
Run/Stop control is local to
inverter
Run/Stop control is from
network host polled I/O
6
Network Reference
Output freq. / accel / decel is
from F_01, F_02, F_03
Output freq. / accel / decel is
from network host polled I/O
7
Frequency Arrival
Inverter stopped, or in accel or
decel
Inverter output arrived at
target freq.
Inverter Produced Data, (Host) Input Instance (P_47) = 101
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Input
term. [3]
Input
term. [2]
Input
term. [1]
Freq.
Arrival
—
Trip
RV Run
FW Run
1
Inverter status (see status code table, next page)
2
Output frequency monitor (low byte), D_01 value
3
Output frequency monitor (high byte), D_01 value
4
Output current monitor (low byte), D_02 value
5
Output current monitor (high byte), D_02 value
6
Trip error code, D_08 value
7
—