SJ100DN Inverter
29
To the 18 option codes for standard SJ100 inverters, SJ100DN Series inverters remove
the code for the [AT] input, and add the following 5 options:
NOTE:
The assignment of [DNT] to an input terminal is optional. It is useful if you
need to switch between DeviceNet network control and local control during running.
Alternatively, you can use parameter P_43 DeviceNet Control Enable, which works
similarly but does not require an input terminal. If assigned, the [DNT] setting has prece-
dence over the P_43 setting. More information is in “Step 7 – Control Test – Verify
Network Host Can Control Inverter” on page 54.
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
20
STA
Start Motor
ON
Start motor rotation on momentary contact (uses
acceleration profile)
OFF
No change to motor operation
21
STP
Stop Motor
ON
Stop motor rotation on momentary contact (uses
deceleration profile)
OFF
No change to motor operation
22
F/R
FWD/REV
ON
Select reverse direction of rotation
OFF
Select forward direction of rotation
25
DNT
DeviceNet Select
ON
Inverter operates under DeviceNet network
control
OFF
Inverter operates under local control (keypad and
input terminals)
31
OPE
Force Operation
from Digital
Operator
ON
Forces the operator interface Run command to
over-ride commands from input terminals (such
as [FW], [RV])
OFF
Run command operates normally, as configured
by A_02