Chapter 13 – The optional remote operators
13-4
Standard setting
Funct.
No.
Function Display
-FE -FU
Parameter
range
Refer
to
Overload limit current
OLOAD LVL 20.63A
Rated
current
*1,25
Rated
current
*1,25
50~150% of
rated current
b 22
Deceleration rate
OLOAD CONST 01.0
1.0 1.0 0.1~30
b 23
F-24
Overload limit characteristic
OLOAD MODE
ON
ON ON
OFF, ON,
CRT
b 21
F-25
Software lock mode
S-LOCK MD1
MD1 MD1
MD0, MD1,
MD2, MD3
b 31
Frequency lower limit
LIMIT L
000.0Hz
0Hz 0Hz 0~360
A 62
F-26
Frequency upper limit
LIMIT H
000.0Hz
0Hz 0Hz 0~360
A 61
1. jump frequency
JUMP F1
000.0Hz
0Hz 0Hz 0~360
A 63
2. jump frequency
JUMP F2
000.0Hz
0Hz 0Hz 0~360
A 65
3. jump frequency
JUMP F3
000.0Hz
0Hz 0Hz 0~360
A 67
1. jump frequency width
JUMP W1
00.5Hz
0.5Hz 0.5Hz 0~10
A 64
2. jump frequency width
JUMP W2
00.5Hz
0.5Hz 0.5Hz 0~10
A 66
F-27
3. jump frequency width
JUMP W3
00.5Hz
0.5Hz 0.5Hz 0~10
A 68
F-28
STOP key locking
STOP-SW ON
ON ON ON,
OFF
b 87
External frequency start point
IN EXS
000.0Hz
0Hz 0Hz 0~360
A 11
External frequency end point
IN EXE
000.0Hz
0Hz 0Hz 0~360
A 12
External frequency start point bias
IN EX%S
000%
0% 0% 0~100
A 13
External frequency end point bias
IN EX%E
100%
100% 100% 0~100
A 14
External frequency start pattern
IN LEVEL
0Hz
0Hz 0Hz 0Hz/EXS
A 15
F-31
Analog input filter time constant
IN F-SAMP
8
8 8 1~8
A 16
Arrival frequency FA2 for
acceleration
ARV ACC
000.0Hz
0Hz 0Hz 0~360
C 42
F-32
Arrival frequency FA2 for
deceleration
ARV DEC
000.0Hz
0Hz 0Hz 0~360
C 43
Level for overload signal
OV Load
16.50A
Rated
current
Rated
current
Rated current
* 0~200%
C 41
F-33
Level of PID deviation
OV PID
003.0%
3% 3% 0~100
C 44
Function of digital input 1
IN-TM 1
FW
FW FW
C 01
Function of digital input 2
IN-TM 2
RV
RV RV
C 02
Function of digital input 3
IN-TM 3
CF1
CF1 AT
C 03
Function of digital input 4
IN-TM 4
CF2
CF2 USP
C 04
Function of digital input 5
IN-TM 5
RS
RS RS
For a des-
cription of
parameters
please refer
to chapter 7
C 05
Type of digital input 1
IN-TM O/C-1
NO
C 11
Type of digital input 2
IN-TM O/C-2
NO
C 12
Type of digital input 3
IN-TM O/C-3
NO
C 13
Type of digital input 4
IN-TM O/C-4
NO
C 14
F-34
Type of digital input 5
IN-TM O/C-5
NO
NO NO NO,
NC
C 15
Function of digital output 11
OUT-TM 1
FA1
FA1 FA1
C 21
Function of digital output 12
OUT-TM 2
RUN
RUN RUN
RUN, FA1,
FA2, OL,
OD, AL
C 22
Type of alarm relay output
OUT-TM O/C-A
NC
NC NC NO,
NC
C 33
Digital output 11 type
OUT-TM O/C-1
NC
C 31
F-35
Digital output 12 type
OUT-TM O/C-2
NC
NC NC NO,
NC
C 32