Chapter 13 – The optional remote operators
13-3
The function mode
When the remote operator DOP or the copy unit DRW is connected to an L100IP series inverter the
parameters listed in the following table can be configured.
Standard setting
Funct.
No.
Function Display
-FE -FU
Parameter
range
Refer
to
F-00 Base
frequency
F-BASE 050Hz
50Hz 60Hz 50~360
A 03
F-01 Maximum
frequency
F-MAX 050Hz
50Hz 60Hz 50~360
A 04
F-02 Start
frequency
Fmin 0.5Hz
0.5Hz 0.5Hz 0.5~9.9
b 82
Motor voltage
for AVR function
AVR AC
200V
230/400V 230/460V
200, 220,
230,
240/380,
400, 415,
440, 460
A 82
F-03
AVR function characteristic
AVR MODE
DOFF
DOFF DOFF ON, OFF,
DOFF
A 81
F-04 Voltage/frequency
characteristic
CONTROL VC
VC VC VC,
VPI
A 44
1. Acceleration time
ACC1 0010.0s
10.0s 10.0s 0.1~3000
F 02
Method to switch over
from 1. to 2. accel/decel time
ACC CHG
TM
TM TM TM,
FRE
A 94
2. Acceleration time
ACC2 0015.0s
15.00s 15.00s 0.1~3000
A 92
Accel.1 / Accel.2
switchover frequency
ACC CHFr 000.0Hz
0.0Hz 0.0Hz 0~360
A 95
F-06
Acceleration characteristic
ACC LINE
L
L L L,
S
A 97
1. Deceleration time
DEC1 0010.0s
10.0s 10.0s 0.1~3000
F 03
2. Deceleration time
DEC2 0015.0s
15.0s 15.0s 0.1~3000
A 93
Decel.1 / Decel.2
switchover frequency
DEC CHFr 000.0Hz
0.0Hz 0.0Hz 0~360
A 96
F-07
Deceleration characteristic
DEC LINE
L
L L L,
S
A 98
F-10 Operation method after FRS cancelled
RUN FRS
ZST
ZST ZST fST,
ZST
b 88
Multistage frequency setting 1
SPD 1
005.0Hz
0Hz 0Hz 0~360
A 21
Multistage frequency setting 2
SPD 2
005.0Hz
0Hz 0Hz 0~360
A 22
Same for multistage frequency settings 3 – 14
A 23 ... A 34
F-11
Multistage frequency setting 15
SPD15 005.0Hz
0Hz 0Hz 0~360
A 35
DC brake active / not active
DCB SW
OFF
OFF OFF ON,
OFF
A 51
DC brake frequency
DCB F
00.5Hz
0.5Hz 0.5Hz 0.5~10
A 52
DC brake waiting time
DCB WAIT
0.0s
0.0s 0.0s 0~5
A 53
DC brake braking torque
DCB V
000
0 0 0~100
A 54
F-20
DC brake braking time
DCB T
00.0s
0.0s 0.0s 0~60
A 55
Allowable undervoltage failure time
IPS UVTIME
01.0s
1.0s 1.0s 0.3~25
b 02
Waiting time until retry
IPS WAIT
010.0s
1.0s 1.0s 0.3~100
b 03
F-22
Restart mode
IPS POWR
ALM
ALM ALM
ALM, FTP,
RST, ZST
b 01
Electronic thermal
characteristic
E-THM CHAR
SUB
CRT CRT
CRT,
SUB
b 13
F-23
Electronic thermal
protection current
E-THM LVL
16.50A
Rated
current
Rated
current
50~120% of
rated current
b 12