Chapter 5 – Wiring
5-7
The following table shows the location and dimensions of control and alarm terminals:
Location of terminals
(REMOVABLE CONNECTOR)
Screw size
(Screwdriver type)
Cross section
of cable
Tightening
torque range
M2
(0.4x2.5mm)
0.5…1.5mm
2
(AWG 22...14)
0.2...0.25 Nm
M2.5
(0,6x3,5mm)
0,5-2.5mm
2
(AWG 22..12)
0.4…0.5 Nm
In the following table the purpose of the power terminals is shown:
Terminal symbol
Purpose
Description
L1, L2, L3
(L, N)
Mains supply
Single phase supply: connect to L, N
Three phase supply: connect to: L1, L2, L3
U, V, W
Inverter output
Connect a three phase motor
+, -
Braking unit
Connect the optional braking unit (when high
braking torque is required).
Grounding
Ground must be connected to prevent electric shock
should the inverter case carry dangerous voltages
due to a malfunction. Also to connect cable shield.
L1
(L)
L2 L3
(N)
U
V
W
Motor
The following table lists the tightening torque values for tightening the screws:
Screw
Torque in Nm
M2
Typ. 0.20 Max. 0.25
M3
Typ. 0.50 Max. 0.60
M3.5
Typ. 0.80 Max. 0.90
M4
Typ. 1.20 Max. 1.30
M5
Typ. 2.00 Max. 2.20
The next table describes the purpose of each control terminal: (
To be continued on next page
)
Terminal
category
Sym
bol
Purpose Initial
setting
Remarks
5 Reset
input
4
Multistage frequency
input / USP function
3
Multistage frequency
input / use 4-20mA input
2 Reverse
run
1
These inputs have different purposes
depending on the user programmed
configuration:
Forward and reverse running command,
up to 4 multistage speed settings,
jogging run, 2nd stage acceleration/decel.,
free run stop, external trip, USP function,
terminal software lock, reset, PTC, input
for choosing current as analogue set value
Forward run
Input closed (ON):
Function active
Input opened (OFF):
Function not active
Input must be ON for a
minimum of 12ms
Digital
Inputs
P24
Common for input signals
24V DC; max. 30mA
FM
Connection of an analogue or digital meter
for measuring frequency;
connection of an analogue meter for
current measurement
Frequency monitor
(analogue)
Monitor
signal
L
Common for monitor signal
L
3
4
5
2
1
H
O
OI
FM
L
12 11