Chapter 11 – Technical specifications
11-3
Notes on technical specifications:
Note 1
: Protective structure is based upon EN60529
Note 2
: The applicable motor is a Hitachi standard four-pole motor. When using another motor, make
sure that the rated motor current does not exceed the rated inverter current.
Note 3
: The output voltage will decrease if input voltage decreases.
Note 5
: Confirm with the motor manufacturer the motors maximum rpm when using a motor running
at frequencies higher than 50/60Hz
Note 6
: Torque will be reduced when the base frequency exceeds 50Hz.
Note 7
: The weight is based on the L100IP-XFE 510 version (with filter).
Power supply
(three phase)
50/60 Hz
Fuses
L100IP series
inverter
L1 (L)
L2
L3 (N)
U
V
W
1
2
3
4
5
L
P24
H
O
OI
L
FM
AL0
AL1
AL2
11
CM2
12
Motor
Ground
Alarm signal
(relay output)
°
C
Thermistor
Frequency
monitor
Set value input
4 – 20 mA
Analog set value 0 – 10V
(Pot 1k – 2k Ohm)
Power supply
Running command
Output frequency
> 2 s
The common potential depends
on the terminals used:
Terminals
Common
potential
1, 2, 3, 4, 5
P24
FM, H, O, OI
L
11, 12
CM2
Notes:
24VDC
A trip will occur when a running command is active at the time the
power supply is switched on. The power supply should not be
switched on simultaneously with the running command; instead
there should be a time delay of about 2 seconds from the time the
power supply is switched on until the running command is activated
(refer to time diagram). Also the power supply must not be switched
off while the running command is being active (motor is running).