Chapter 12 – Wiring examples
12-1
Chapter 12 – Wiring examples
Set value supplied by external potentiometer
Connection diagram
Re
verse
run
Fo
rw
ar
d r
un
24VDC
Frequency monitor
(0..10V, 1mA)
Potentiometer
1 ... 2kOhm
Configuration of parameters
Function
Configurable
parameters
Description
A 01
01
Set value input using control terminals
A 02
01
Running command using terminals FW/RV
F 02
10
Acceleration time in s
F 03
10
Deceleration time in s
C 01
00
FW: Forward running command on digital input 1
C 02
01
RV: Reverse running command on digital input 2
C 23
00
Monitoring of output frequency (analog) using the
meter connected to terminals L and FM.
b 81
80
Adjustment of the frequency meter connected to
terminals L and FM
Function description
The inverter can now be started via input 1 (forward run) or input 2 (reverse run). If
the inputs RV and FW are both closed, the inverter is stopped.
By adjusting the external potentiometer the desired frequency set value (voltage set
value) can be set.
The analog meter can be used to display the frequency (parameter 00 must be set
under
C 23
) or the motor current (parameter 01 must be set under
C 23
). With
function
b 81
the displayed frequency or current value can be adjusted to the
measuring range of the special meter used.