System Manual Modular Systems
8 Operation
HI 800 191 E Rev. 2.02
Page 99 of 114
source and code are displayed in the feedback box for the diagnosis. This message helps
analyzing errors due to an incorrect configuration of the inputs or outputs.
If the memory for the short-term diagnosis is full, the oldest entries are deleted to allow new
data to be saved. No message appears warning that old entries are being deleted.
Diagnostic data recording is not safety-related. To read the data recorded in chronological
order, use the programming tool. Reading does not delete the data stored in the controller. The
programming tool is capable of storing the contents of the diagnostic window.
8.2.3
Diagnosis in SILworX- CPU OS V7 and Higher
Use the Online View in the SILworX Hardware Editor to access to the diagnostic panel.
To open the diagnostic panel
1. Select the
Hardware
branch located beneath the required resource.
2. Click
Online
on the context menu or on the Action Bar.
The system log-in window opens.
3. In the system log-in window, select or enter the following information:
-
IP address of the controller
-
User name and password.
The Hardware Editor's Online View opens.
4. In the Online View, select the required module, usually the processor or the communication
module.
5. Select
Diagnosis
from the context menu or the
Online
menu.
The diagnostic panel for the required module appears.
If a controller is operating, messages about the state of the processor system, communication
system and I/O modules are displayed at specific, user-defined time intervals.
8.2.4
Diagnosis in ELOP II Factory - up to CPU OS V7
Select the corresponding resource in the ELOP II Factory's Hardware Management to access
the diagnostic panel.
To open the diagnostic panel
1. Select and right click the required resource.
2. Select
Online,
and then select
Diagnosis
.
3. If not yet already done, log in to the resource in the corresponding window.
The diagnostic panel appears.
If a controller is operating, messages about the state of the processor system, communication
system and I/O modules are displayed at specific, user-defined time intervals.