7 Start-Up
System Manual Modular Systems
Page 56 of 114
HI 800 191 E Rev. 2.02
Parameter
Description
Default
value
Setting for safe
operation
Allow Online
Settings
ON:
All the switches/parameters listed below OFF
can be changed online using the PADT.
ON
OFF is
recommended
OFF:
These parameters may
not
be changed online
System ID
Autostart
Global Forcing
Allowed
Global Force
Timeout Reaction
Load Allowed
Reload Allowed
Start Allowed
These parameters may
be changed online if
Reload Allowed
is set
to ON.
Watchdog Time
(for
the resource)
Safety Time
Target Cycle Time
Target Cycle Time
Mode
If
Reload Allowed
is set
to OFF, they are not
changeable online.
i
Allow Online Settings
can only be set to ON if
the PES is stopped.
Autostart
ON:
If the processor module is connected to the
supply voltage, the user program starts
automatically
OFF
Application-
specific
OFF:
The user program does not start automatically
after connecting the supply voltage.
Start Allowed
ON:
A cold start or warm start permitted with the
PADT in RUN or STOP
ON
Application-
specific
OFF:
Start not allowed
Load Allowed
ON:
Configuration download is allowed
ON
Application-
specific
OFF:
Configuration download is not allowed
Reload Allowed
Only applicable with F*03 devices/modules!
ON
Application-
specific
ON:
Configuration reload is allowed
OFF:
Configuration reload is not allowed.
A running reload process is not aborted when
switching to OFF
Global Forcing
Allowed
ON:
Global forcing permitted for this resource
ON
Application-
specific
OFF:
Global forcing not permitted for this resource
Global Force
Timeout Reaction
Specifies how the resource should behave when the global
force timeout has expired:
Stop Forcing
Stop the Resource
Stop
Forcing
Application-
specific
Minimum
Configuration
Version
With this setting, code compatible to previous or newer
CPU operating system versions in accordance with the
project requirements may be generated.
SILworX
V5 with
new
projects
Application-
specific
SILworX
V2
The code is generated as in SILworX V2. With
this setting, the use of the code on standard
devices and modules is supported for CPU
operating system V7.
SILworX
V3
Not applicable for HIMatrix controllers!
SILworX
V4
The generated code is compatible to the CPU
operating system V8.
SILworX
V5
Corresponds to
SILworX V4.
This setting
ensures the compatibility with future versions.