7 Start-Up
System Manual Modular Systems
Page 76 of 114
HI 800 191 E Rev. 2.02
The parameters of the Boolean events must be entered in a table with the following columns:
Column
Description
Range of values
Name
Name for the event definition; it must be unique within the
resource.
Text, max. 32
characters
Global Variable
Name of the assigned global variable (added using a drag&drop
operation)
Data Type
Data type of the global variable; it cannot be modified.
BOOL
Event Source
CPU event The processor module creates the timestamp. It
creates all the events in each of its cycles.
Auto event As CPU event
Default value: Auto Event
CPU, Auto
Alarm when
FALSE
Activated
If the global variable value changes from TRUE to
FALSE, an event is triggered.
Deactivated If the global variable value changes from FALSE to
TRUE, an event is triggered.
Default value: Deactivated
Checkbox activated,
deactivated
Alarm Text
Text specifying the alarm state
Text
Alarm priority
Priority of the alarm state
Default value: 500
0...1000
Alarm
Acknowledgment
Successful
Activated
The alarm state must be confirmed by the user
(acknowledgement)
Deactivated The alarm state may not be confirmed by the user
Default value: Deactivated
Checkbox activated,
deactivated
Return to Normal
Text
Text specifying the alarm state
Text
Return to Normal
Severity
Priority of the normal state
Default value: 500
0...1000
Return to Normal
Ack Required
The normal state must be confirmed by the user
(acknowledgement)
Default value: Deactivated
Checkbox activated,
deactivated
Table 42: Parameters for Boolean Events