7 Start-Up
System Manual Modular Systems
Page 96 of 114
HI 800 191 E Rev. 2.02
7.9.6
Online Test
The
Online Test
function is used to add online test fields (OLT fields) to the program logic, to
display and to force signals/variables while the controller is operating.
If the
Online Test Allowed
switch is on, the values of signals/variables can be manually entered
in the corresponding OLT fields and thus forced. However, the forced values only apply until
they are overwritten by the program logic.
If the
Online Test Allowed
switch is off, the values of the signals/variables in OLT fields are only
displayed and cannot be modified.
For more information on how to use OLT fields, enter
OLT field
in the online help of the
programming tool.