System Manual Modular Systems
7 Start-Up
HI 800 191 E Rev. 2.02
Page 83 of 114
The following table specifies the switch signals used in the example:
Name
Type
Description
Remark
S1_1_pulsed
S1_2_pulsed
BOOL
BOOL
Value
Value
First and second contact of
switch 1
S2_1_pulsed
S2_2_pulsed
BOOL
BOOL
Value
Value
First and second contact of
switch 2
FC_S1_1_pulsed
FC_S1_2_pulsed
BYTE
BYTE
Error code
Error code
Error codes for first and second
contact of switch 1
FC_S2_1_pulsed
FC_S2_2_pulsed
BYTE
BYTE
Error code
Error code
Error codes for first and second
contact of switch 2
Table 48: Switch Signals for Line Control
The following table specifies the slot numbers of modules with pulsed outputs when compact
devices are used.
Device
System signal
DI Pulse Slot.
F1 DI 16 01
1
F3 DIO 8/8 01
3
F3 DIO 16/8 01
3
F3 DIO 20/8 02
2
F20
2
F30
2
F31
2
Table 49: Module Slot with Pulsed Outputs
If the modular F60 system is used, the number of the slot in which the module with pulsed
outputs is inserted, must be used (3…8).
7.7.4.2
Configuring Pulsed Outputs
The pulsed outputs must begin with
DO[01].Value
and reside in direct sequence, one after the
other:
ELOP II Factory
outputs
Examples of permitted configurations ...
... of not permitted
DO[01].Value
A1
Pulse_ON
Pulse_ON Pulse_ON A1
Pulse_ON
DO[02].Value
A2
Pulse_ON
Pulse_ON Pulse_ON Pulse_ON Pulse_ON
DO[03].Value
A3
Pulse_ON
Pulse_ON Pulse_ON Pulse_ON A3
DO[04].Value
A4
A4
Pulse_ON Pulse_ON Pulse_ON Pulse_ON
DO[05].Value
A5
A5
A5
Pulse_ON Pulse_ON Pulse_ON
DO[06].Value
A6
A6
A6
Pulse_ON A6
Pulse_ON
DO[07].Value
A7
A7
A7
A7
A7
A7
DO[08].Value
A8
A8
A8
A8
A8
A8
Table 50: Configuration of Pulsed Outputs in ELOP II Factory
The corresponding inputs can be freely selected, i.e., two consecutive pulsed outputs need not
be assigned to two adjacent inputs.
Restriction:
Two adjacent inputs may not be supplied from the same pulse to prevent crosstalk.
7.7.4.3
Configuration Example with ELOP II Factory
Basic Method for Assigning Signals
If ELOP II Factory is used, the signals previously defined in the Signal Editor (Hardware
Management) are assigned to the individual hardware channels (inputs and outputs).