System Manual Modular Systems
7 Start-Up
HI 800 191 E Rev. 2.02
Page 61 of 114
Variable
Description
Data
Type
OFF: Loading by performing a reload is possible
Reload Cycle
With F*03 devices only!
TRUE during the first cycle after a reload, otherwise FALSE
BOOL
CPU Safety Time [ms]
Safety time set for the controller in ms
UDINT
Start Allowed
ON:
Start of processor system using PADT is allowed
BOOL
OFF: Start of processor system using PADT is not allowed
Start Cycle
ON during the first cycle after starting, otherwise OFF
BOOL
Power Supply State
Bit-coded state of the power supply units.
Compact controllers and remote I/Os:
Value
State
0x00
Normal
0x01
Undervoltage with 24 V supply voltage
0x02
(Low voltage with battery)
not used
0x04
Low voltage with internally generated 5 V voltage
0x08
Low voltage with internally generated 3.3 V voltage
0x10
Overvoltage with internally generated 3.3 V voltage
F60 modular controller:
Value
State
0x00
Normal
0x01
Error with 24 V supply voltage
0x02
Battery failure
0x04
Error with 5 V voltage of power supply
0x08
Error with 3.3 V voltage of power supply
0x10
Undervoltage with 5 V voltage
0x20
Overvoltage with 5 V voltage
0x40
Undervoltage with 3.3 V voltage
0x80
Overvoltage with 3.3 V voltage
BYTE
System ID [SRS]
System ID of the controller, 1...65 535
UINT
Systemtick HIGH
Revolving millisecond counter (64-bit)
UDINT
Systemtick LOW
UDINT
Temperature state
Bit-coded temperature state of the processor system
Value
State
0x00
Normal temperature
0x01
Temperature threshold 1 exceeded
0x03
Temperature threshold 2 exceeded
0xFF
Not available
BYTE
Remaining Global Force
Duration [ms]
Time in ms until the time limit set for global forcing expires.
DINT
Watchdog Time [ms]
Maximum permissible duration of a RUN cycle in ms.
UDINT
Cycle Time, last [ms]
Current cycle time in ms
UDINT
Cycle Time, max [ms]
Maximum cycle time in ms
UDINT
Cycle Time, min [ms]
Minimum cycle time in ms
UDINT
Cycle Time, average [ms]
Average cycle time in ms
UDINT
Table 30: Hardware System Variables for Reading the Parameters